Technical data
Electrical data
EL 1xx CAN/PLC/MPI
4
21
LDCDS−EL100 EN 9.0
PLC functions
(EN 61131−3)
Typ EL xxx PLC
105m 105 106 108 110 110s
Editor AWL, FUP, KOP, ST, AS, CFC
Program code [kB] 2048
Data memory
Variables
Global Var.
[kB]
[kB]
1024
512
Memory location [kB] 4
Process image
Input
Output
[kB]
[kB]
4
4
Retain data [kB] 128
UPS Integrated to save retain data to the flash memory
Target
L−force Logic
EL1xx
V1.x
Task runtime [ms] ³10
Ports
COM 1
Type
RS232
Connection SUB−D, 9−pole, connector
LAN
Type Ethernet
Protocol TCP/IP
Baud rate 10/100 Mbits
Connection RJ45, socket
USB
Type 2.0 (1.1−compatible)
Connection Type A and type B, socket
CAN
1)
Type CAN, ISO11898
Protocol Lenze system bus CAN
Topology Line, terminated on both sides with 120 W
Node Master or slave
Number of nodes Max. 63
Baud rate See CAN communication manual
Bus length See CAN communication manual
Connection SUB−D, 9−pole, connector
MPI
1)
Type RS485
Protocol MPI
Topology Line, terminated on both sides with 200 W
Node Master
Number of nodes Max. 32 per segment
Max. 127 with RS485 repeaters
Baud rate 19.2 kBaud ... 12 MBaud
Bus length Max. 50 m
Connection SUB−D, 9−pole, connector