Mechanical installation
Important notes
3
73
EDKCSCE040 DE/EN/FR 3.0
3 Mechanical installation
3.1 Important notes
ƒ ECS power supply modules are provided with IP20 enclosure and can
therefore only be used for installation in control cabinets.
ƒ If the cooling air contains air pollutants (dust, fluff, grease, aggressive
gases):
Take suitable preventive measures , e.g. separate air duct, installation
of filters, regular cleaning.
ƒ Possible mounting positions
Vertical at the mounting plate
DC bus connections (X22) at the top
Mains connection (X21) at the bottom
ƒ Maintain the specified clearances (above and below) to other
installations!
If the ECSZS000X0B shield mounting kit is used, an additional clearance
is required.
Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
Several modules of the ECS series can be installed in the control cabinet
next to each other without any clearance.
ƒ The mounting plate of the control cabinet
must be electrically conductive.
must not be varnished.
ƒ In case of continuous vibrations or shocks use shock absorbers.
Vedere la pagina 72