Lenze EPM−T9XX Modular system Manuale Utente Pagina 488

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 544
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 487
Parameterising 2/4xcounter module
Encoder with GATE (modes 36 ... 38)
13
Parameter setting via PROFIBUS−DP
13.2
13.2.19
L
13.2−54
EDSPM−TXXX−9.0−11/2009
The counter is incremented by 1 on
l a LOW−HIGH edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
l a HIGH−LOW edge (track A) at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
epm−t168
Fig. 13.2−75 Signal characteristic of 2/4xcounter in the mode 37 (upcounter)
The counter is decremented by 1 on
l a LOW−HIGH edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).
l a HIGH−LOW edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).
epm−t169
Fig. 13.2−76 Signal characteristic of 2/4xcounter in the mode 37 (downcounter)
Signal characteristic in mode 37
Vedere la pagina 487
1 2 ... 483 484 485 486 487 488 489 490 491 492 493 ... 543 544

Commenti su questo manuale

Nessun commento