6.5.7 Reading a parameter
FC4, network 3
UN “TriggerRead”
= “TriggerRead”
CALL FC 90 //data types
DrivePar_DB :=”S7-Parameter” //DB81
Count :=0 //decimal: 0-31
PB_Address :=”PB-Address” //B#16#9
R_W :=TRUE //FALSE or TRUE
Code :=”Code” //W#16#C, code 12
SubCode :=”Subcode” //B#16#0, Sub-code 0
W_Value :=”Value” //DINT oder L#xxx
Status :=”ReadStatus” //OUT, BYTE, status byte
R_Value :=”ReadValue” //OUT, DINT, value
Trigger :=”TriggerRead” //INOUT, BOOL
• The variable TriggerRead is always set to TR UE.
Once a parameter read request has been processed correctly, TriggerRead is automatically
reset to FALSE.
• FC90 and parameter R_W = TRUE are called to transmit a read request for a drive parameter.
• Data exchange with FB DRIVE (FB90) takes place via the da ta block S7-Parameter (DB81).
• Input parameters are the request number, PROFIBUS address, write/read request and the code
and sub-code to be read.
• Output parameters are the read value and the status byte.
• Set parameter R_W to FALSE to transmit a write request for a drive parameter.
Tip!
Detailed information about the parameters of FC90 can be found in cha pter 6.3.3. (^ 102)