Drive PLC
Appendix
8.5 System error messages
8−15
L
DrivePLC DE 6.0
Fault reset
The current fault can be reset by a TRIP−RESET e.g. via C0043:
Code LCD
Possible settings
Info
Lenze Selection
C0043 Trip reset 0 TRIP reset
0 TRIP−RESET (current TRIP reset)
1 Error occurred (TRIP is active)
Deleting entries in the fault memory
The entries in the fault memory can be deleted via C0167.
This function can only be used if there is no active fault.
Code LCD
Possible settings
Info
Lenze Selection
C0167 Reset failmem 0 Reset fault memory
0 No function
1 Delete all entries in history buffer
8.5.6 Error analysis via the PLC LED
Two LEDs at the front of the PLC indicate the controller status:
LED green LED red Controller status Check test
−− « Warning C0183, C0168/1
−− «« Message C0183, C0168/1
−− n Error: TRIP C0183, C0168/1
«« o PLC program not loaded C0183, C0168/1
o o PLC program loaded
n o PLC program running
« o PLC program loaded but stopped
n on o off «blinking (every second) ««blinking (every 0.5 s) −− Status without meaning
8.5.7 Fault analysis via the 9371BB keypad
Displayed status messages indicate the controller status:
Display Controller status Check test
RDY PLC ready for operation C0183, C0168/1
Fail Error indicated by TRIP, message or warning