DMS 3.1 EN 01/2011 TD17 L 117
Control technology | EtherCAT communication manual
EtherCAT function libraries
Function blocks and functions for diagnosing the network
The L_ECAT_ErrCnt structure
The L_ECAT_ErrCnt structure contains the error counters of the single ports of a connected
device.
9.7.7 L_ECAT_ResetErrCnt (FB)
Inputs (VAR_INPUT)
Outputs (VAR_OUTPUT)
TYPE L_ECAT_ErrCnt :
STRUCT
Port0 : BYTE;
Port1 : BYTE;
Port2 : BYTE;
Port3 : BYTE;
END_STRUCT
END_TYPE
Identifier/data type Description
Port[n]
BYTE
Error counter value of the errors recorded at the port[n]
n: 0 ... 3
Function: This function block resets the telegram error counters of all connected
slaves (see Error counters of the EtherCAT slaves
( 143)). This block
should be executed before one of the telegram error counters of the
slaves has reached the maximum value of 255.
Library: SM_Ethercat.lib
Visualisation: VISU_L_ECAT_ResetErrCnt
Identifier/data type Meaning/possible settings
bExecute
BOOL
The function block is activated in an edge-controlled manner:
• Positive edge (TRUE) = function block is executed.
Identifier/data type Meaning/possible settings
bDone
BOOL
FALSE: Function block is active or has not been called
TRUE: Function block has been executed.
bError
BOOL
FALSE: No error
TRUE: An error has occurred.
dwErrorID
DWORD
Display of a hexadecimal error code (see also System error messages
( 157)) if an
error has occurred (bError =TRUE).
Commenti su questo manuale