3.6 Code table
9300 Servo PLC
Appendix
3−134
L
9300 Servo PLC EN 5.1
Code InformationPossible settingsLCDCode Information
SelectionLenze
LCD
C0356 CAN boot−up System bus: Time settings
1 3000 0 {1 ms} 65000 Delay time after power−on for initialisation through the
quasi" master.
2 0 0 {1} 65000
0 = event−controlled transmission
Task time factor for sending the CAN2_OUT process data
object.
3 0 Task time factor for sending the CAN3_OUT process data
object.
4 20 0 {1 ms} 65000 Delay time for sending the process data object.
C0357 CE monit time System bus: Monitoring time for process data input objects
0 {1 ms} 65000
1 3000 CE1monit time
2 3000 CE2monit time
3 3000 CE3monit time
C0358 Reset node 0 System bus: Reset node
0 No function
1 CAN reset node
C0359 CAN state
g
System bus: Status
0 Operational
1 Pre−operational
2 Warning
3 Bus off
4 Stopped
C0360 CAN message
g
System bus: Telegram counter
(number of telegrams)
For values > 65535 counting restarts with 0
0 {1 ms} 65535
1 All sent (without free CAN objects)
2 All received (without free CAN objects)
3 Sent to CAN1_OUT
4 Sent to CAN2_OUT
5 Sent to CAN3_OUT
6 Sent to parameter data channel 1
7 Sent to parameter data channel 2
8 Received by CAN1_IN
9 Received by CAN2_IN
10 Received by CAN3_IN
11 Received by parameter data channel 1
12 Received by parameter data channel 2
C0361 Load IN/OUT
g
System bus: Bus load
Trouble−free operation demands that the total bus load
(all connected devices) does not exceed 80 %.
0 {1 %} 100
1 All sent (without free CAN objects)
2 All received (without free CAN objects)
3 Sent to CAN1_OUT
4 Sent to CAN2_OUT
5 Sent to CAN3_OUT
6 Sent to parameter data channel 1
7 Sent to parameter data channel 2
8 Received by CAN1_IN
9 Received by CAN2_IN
10 Received by CAN3_IN
11 Received by parameter data channel 1
12 Received by parameter data channel 2