Electrical installation
Control terminals
Important notes
5
l
91
EDKVF9338 DE/EN/FR 4.0
How to connect the shield
3
10
2
9300vec063
Fig. 5−9 Connection of the cable shield with shield clip and strain relief with cable binder
0 Shield sheet
1 Fasten shield sheet with two screws M4 × 12 mm at the bottom of the control card
2 Connect cable shield with shield clip to the shield sheet
3 Provide a strain relief of the control cable at the shield sheet by means of a cable binder
Terminal data
( Stop!
ƒ Connect or disconnect the terminal strips only if the controller is
disconnected from the mains!
ƒ Wire the terminal strips before connecting them!
ƒ Unused terminal strips must also be plugged on to protect the contacts.
Cable type Wire end ferrule Maximum cable
cross−section
Tightening torque Stripping
length
Rigid 2.5 mm
2
(AWG 14)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
5 mm
Flexible
Without wire end
ferrule
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule
without plastic sleeve
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule with
plastic sleeve
2.5 mm
2
(AWG 14)