PLC Designer V2.x| Lenze Application Samples
The L_SSC_Scaling.lib library
L_SSC_GetPosition - conversion block
318 L 1.3 EN - 07/2012
20.3 L_SSC_GetPosition - conversion block
This FB converts the input signal transmitted to a position signal.
Inputs
Outputs
Identifier/data type Information/possible settings
diPosIn_p
DINT
Position in [increments]
Scaling: 1 encoder revolution 2
16
increments (or according to scAxisData)
scAxisData
SSC_Axis_logic
Machine parameters
Identifier/data type Information/possible settings
rPositionOutUnits
REAL
Position value
Display of the input signal dnPosIn_p in the real unit of the machine.
xError
BOOL
"Error" status signal
FALSE Conversion carried out without errors
TRUE Error during the conversion