Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17 100
14 Diagnostics
14.4 System bus configurator of the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.4 System bus configurator of the »Engineer«
1. First directly connect your notebook via the USB system bus adapter EMF2177IB to the
CANopen bus.
2. Start the system bus configurator ...
•via the Online button in the menu bar of the »Engineer«
or under "Start - Programs - Lenze - Communication"
3. Activate the USB system bus adapter (EMF2177IB).
4. Check the following under the Settings tab ...
the baud rate (identical to the setting on the devices)
the parameter data channel (= 0):
The entire address range is scanned. Devices responding on several SDO channels are
displayed with several node addresses.
Example:
5. Click the Communication diagnostics button on the General tab to start the search.