Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17 133
9 Function library L_IODrvEtherCAT.lib
9.2 CoE Interface
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.6 L_ETC_CoE_SdoWrite4 (FB)
This function block triggers downloading of a CoE object (SDO) to the slave or to the master.
Visualisation: VISU_L_ETC_CoE_SdoWrite4
Inputs (VAR_INPUT)
Note!
The function of this function block is identical with the function of
L_ETC_CoE_SdoWrite (FB)
( 131), except that only up to 4 bytes can be written with
L_ETC_CoE_SdoWrite4.
For executing the function block, the EtherCAT master and the slave must be at least
in the "Pre-Operational" state.
L_ETC_CoE_SdoWrite4
BOOL xExecute xDone BOOL
BOOL xAbort xBusy BOOL
USINT usiCom xError BOOL
UINT uiDevice eErrorCode L_ETC_ERRORCODE
WORD wIndex udiSdoAbort UDINT
BYTE bySubindex
UDINT udiTimeOut
ARRAY [0..3] OF BYTE abyData
USINT usiDataLength
Identifier/data type Meaning/possible settings
xExecute
BOOL
A positive edge (TRUE) triggers a write request (downloading) of a CoE object.
xAbort
BOOL
A positive edge (TRUE) aborts a running write request (download).
xAbort is currently not supported in the Lenze control technology R3.x.
usiCom
USINT
EtherCAT master instance number
In the Lenze control technology R3.x, only instance number 1 is currently
supported. usiCom has been pre-assigned with 1, so that the input can be left
open.
A value that does not equal 1 causes the error ETC_E_INVALIDPARM
(0x9811000B).
uiDevice
UINT
EtherCAT address of the master/slave.
The address 0 directly accesses the object directory of the EtherCAT master.
wIndex
WORD
CANopen index to be read in the object directory of the master or slave.
Formula for converting a Lenze code number into a CANopen index: Index =
0x5FFF - code number
bySubindex
BYTE
Subindex in the object directory of the master or slave.
udiTimeout
UDINT
Timeout in milliseconds (ms)
The value 0 is not permissible and causes the error ETC_E_INVALIDPARM
(0x9811000B).