9 Function library L_IODrvEtherCAT.lib
9.2 CoE Interface
134
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Outputs (VAR_OUTPUT)
abyData
ARRAY [0..3] OF BYTE
Memory buffer with the value to be written.
usiDataLength
USINT
Number of the bytes to be written
Identifier/data type Meaning/possible settings
xDone
BOOL
TRUE: An action has been executed successfully.
FALSE: No action active / action is still being executed.
xBusy
BOOL
TRUE: An action is currently being executed.
•FALSE: No action active
xError
BOOL
TRUE: An error has occurred.
•FALSE: No error
eErrorCode
L_ETC_ERRORCODE
Error code of the incorrectly executed action (xError =TRUE).
General error codes (L_ETC_ERRORCODE)
( 183)
SDO abort codes
( 195)
udiSdoAbort
UDINT
If a write request (download) to the slave or master is rejected with an error, here the
CANopen abort code is returned.
Identifier/data type Meaning/possible settings
Vedere la pagina 133