Lenze 9400 Manuale Utente Pagina 645

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 954
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 644
Lenze ยท Servo-Inverter 9400 HighLine ยท Reference manual ยท DMS 10.0 EN ยท 11/2013 ยท TD05/06 645
13 Diagnostics & fault analysis
13.7 Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Inside the device: Fan is defective [0x00770011]
Device utilisation Ixt > C00123 [0x00780000]
Device utilisation Ixt > 100 % [0x00780001]
Motor load Iยฒxt > C00127 [0x00780002]
Motor load Iยฒxt > C00120 [0x00780003]
Module ID (decimal) Error ID (decimal)
119: Temperature monitoring 17
Response (Lenze setting printed in bold) Setting: C00611 (๏ƒพ Adjustable response)
๏ƒพ None ๏‚จ System fault ๏ƒฝ Fault ๏‚จ Trouble ๏‚จ Quick stop by trouble ๏‚จ Warning locked ๏ƒพ Warning ๏‚จ Information
Cause Remedy
Speed of internal fan is too low, e.g. due to dirt. Check/clean fan.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 0
Response (Lenze setting printed in bold) Setting: C00604 (๏ƒพ Adjustable response)
๏ƒพ None ๏‚จ System fault ๏ƒพ Fault ๏‚จ Trouble ๏‚จ Quick stop by trouble ๏‚จ Warning locked ๏ƒฝ Warning ๏‚จ Information
Cause Remedy
Frequent and too long acceleration processes with
overcurrent > C00123
.
Check drive dimensioning.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 1
Response (Lenze setting printed in bold)
๏‚จ None ๏‚จ System fault ๏ƒฝ Fault ๏‚จ Trouble ๏‚จ Quick stop by trouble ๏‚จ Warning locked ๏‚จ Warning ๏‚จ Information
Cause Remedy
Frequent and too long acceleration processes with
overcurrent.
Check drive dimensioning.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 2
Response (Lenze setting printed in bold) Setting: C00606 (๏ƒพ Adjustable response)
๏ƒพ None ๏‚จ System fault ๏ƒพ Fault ๏‚จ Trouble ๏‚จ Quick stop by trouble ๏‚จ Warning locked ๏ƒฝ Warning ๏‚จ Information
Cause Remedy
Motor is thermally overloaded, e.g. due to:
โ€ข impermissible continuous current
โ€ข frequent or too long acceleration processes
โ€ข Check drive dimensioning.
โ€ขCheck setting in C00127
.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 3
Response (Lenze setting printed in bold)
๏‚จ None ๏‚จ System fault ๏ƒฝ Fault ๏‚จ Trouble ๏‚จ Quick stop by trouble ๏‚จ Warning locked ๏‚จ Warning ๏‚จ Information
Cause Remedy
Motor is thermally overloaded, e.g. due to:
โ€ข impermissible continuous current
โ€ข frequent or too long acceleration processes
โ€ข Check drive dimensioning.
โ€ขCheck setting in C00120
.
Vedere la pagina 644
1 2 ... 640 641 642 643 644 645 646 647 648 649 650 ... 953 954

Commenti su questo manuale