_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Inside the device: Fan is defective [0x00770011]
Device utilisation Ixt > C00123 [0x00780000]
Device utilisation Ixt > 100 % [0x00780001]
Motor load Iยฒxt > C00127 [0x00780002]
Motor load Iยฒxt > C00120 [0x00780003]
Module ID (decimal) Error ID (decimal)
119: Temperature monitoring 17
Response (Lenze setting printed in bold) Setting: C00611 (๏พ Adjustable response)
๏พ None ๏จ System fault ๏ฝ Fault ๏จ Trouble ๏จ Quick stop by trouble ๏จ Warning locked ๏พ Warning ๏จ Information
Cause Remedy
Speed of internal fan is too low, e.g. due to dirt. Check/clean fan.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 0
Response (Lenze setting printed in bold) Setting: C00604 (๏พ Adjustable response)
๏พ None ๏จ System fault ๏พ Fault ๏จ Trouble ๏จ Quick stop by trouble ๏จ Warning locked ๏ฝ Warning ๏จ Information
Cause Remedy
Frequent and too long acceleration processes with
overcurrent > C00123
.
Check drive dimensioning.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 1
Response (Lenze setting printed in bold)
๏จ None ๏จ System fault ๏ฝ Fault ๏จ Trouble ๏จ Quick stop by trouble ๏จ Warning locked ๏จ Warning ๏จ Information
Cause Remedy
Frequent and too long acceleration processes with
overcurrent.
Check drive dimensioning.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 2
Response (Lenze setting printed in bold) Setting: C00606 (๏พ Adjustable response)
๏พ None ๏จ System fault ๏พ Fault ๏จ Trouble ๏จ Quick stop by trouble ๏จ Warning locked ๏ฝ Warning ๏จ Information
Cause Remedy
Motor is thermally overloaded, e.g. due to:
โข impermissible continuous current
โข frequent or too long acceleration processes
โข Check drive dimensioning.
โขCheck setting in C00127
.
Module ID (decimal) Error ID (decimal)
120: Analog signal monitoring 3
Response (Lenze setting printed in bold)
๏จ None ๏จ System fault ๏ฝ Fault ๏จ Trouble ๏จ Quick stop by trouble ๏จ Warning locked ๏จ Warning ๏จ Information
Cause Remedy
Motor is thermally overloaded, e.g. due to:
โข impermissible continuous current
โข frequent or too long acceleration processes
โข Check drive dimensioning.
โขCheck setting in C00120
.