14 Parameter reference
14.2 Parameter list | C00120
744
Lenze ยท Servo-Inverter 9400 HighLine ยท Reference manual ยท DMS 10.0 EN ยท 11/2013 ยท TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00120
C00121
C00122
C00123
Parameter | Name:
C00120 | Mot. overload protection (Iยฒxt)
Data type: UNSIGNED_32
Index: 24455
d
= 5F87
h
Threshold for I
2
x t disconnection
โข Disconnection is carried out if the thermal motor load (C00066
) is higher than the set threshold.
โข A 100 % thermal motor load corresponds to a permanently flowing rated motor current
Note:
When the value is parameterised to 200 %, the monitoring mode of the motor overload protection is switched off!
๏ดI2xt motor monitoring
Setting range (min. value | unit | max. value) Lenze setting
0 % 200 105 %
๏พ Read access ๏พ Write access ๏จ CINH ๏จ PLC STOP ๏จ No transfer Scaling factor: 1
Parameter | Name:
C00121 | Warning threshold motor temperature
Data type: UNSIGNED_32
Index: 24454
d
= 5F86
h
Temperature threshold for motor temperature advance warning
โข The response to reaching the threshold can be selected in C00584
.
๏ดMotor temperature monitoring
Setting range (min. value | unit | max. value) Lenze setting
0 ยฐC 150 120 ยฐC
๏พ Read access ๏พ Write access ๏จ CINH ๏จ PLC STOP ๏จ No transfer Scaling factor: 1
Parameter | Name:
C00122 | Heatsink temp. warn. threshold
Data type: UNSIGNED_32
Index: 24453
d
= 5F85
h
Temperature threshold for heatsink temperature advance warning
โข The response to reaching the threshold can be selected in C00582
.
Setting range (min. value | unit | max. value) Lenze setting
0ยฐC8585 ยฐC
๏พ Read access ๏พ Write access ๏จ CINH ๏จ PLC STOP ๏จ No transfer Scaling factor: 1
Parameter | Name:
C00123 | Warning threshold device util.
Data type: UNSIGNED_32
Index: 24452
d
= 5F84
h
Adjustable threshold for I x t advance warning
โข The advance warning is sent if the device utilisation (C00064
) is higher than the set threshold.
โข The response to reaching the threshold can be selected in C00604
.
Setting range (min. value | unit | max. value) Lenze setting
0 % 100 90 %
๏พ Read access ๏พ Write access ๏จ CINH ๏จ PLC STOP ๏จ No transfer Scaling factor: 1